(blue star) Problem

Do I need to use Terminators on a LonWorks Twisted-Pair Network

(blue star) Solution

Termination: What is it?

Termination, is essential on your twisted pair networks (FT-10 and TP-1250).

Verifying Termination

All LonWorks terminators are AC coupled resistors or RC-combinations and present complex impedance to the network. DC-based multi-meter devices are, therefore, not appropriate to measure or verify the correct termination of a LonWorks network. The complex impedance “Z” must be measured using an AC bridge.

It is imperative, in the case of a link power channel, that the link power supply is turned off and fully discharged before any measurements are taken. In the case of power line transceiver based networks, any supply voltage must also be removed.

Measure the impedance between the network cable pair at any point on a channel. Given a measurement at 1 kHz, the readings should be in the magnitude indicated by the following table:

Terminator Placement:

Lab and Manufacturing Testing:

 

(blue star) Related Products