KB1457 - SmartServer Modbus TCP Device Requires At Least One Polled Datapoint

KB1457 - SmartServer Modbus TCP Device Requires At Least One Polled Datapoint

 Problem

When using a Modbus TCP, you need to configure background polling for at least one datapoint in order to keep the TCP connection up and running.  This is necessary even if you don't need the updates. If you don't configure background polling for at least one datapoint then writing to a datapoint on the Modbus device will most likely fail.

 Solution

When using Modbus TCP devices, set the background polling (Datapoint Properties Widget) for 90 seconds for at least one datapoint.

 

 Related Products

SmartServer IoT