SmartConnect 4.2 and higher, OPC UA is a Beta release.
Info

For SmartServer 4.1 and prior, see Using the OPC UA Server with GE Cimplicity (Release 4.1 and Prior).

This section describes the minimal configuration steps required to configure the GE Cimplicity OPC UA client to connect to a SmartServer OPC UA server, and to monitor a datapoint on a device. GE Cimplicity is powerful software for developing HMI/SCADA projects that provide true client-server visualization and control. The latest release includes OPC UA auto-discovery. For more information about GE Cimplicity, go to https://www.ge.com/digital/applications/hmi-scada/cimplicity.

...

Use the procedure that follows to configure to configure the GE Cimplicity OPC UA client to connect to a SmartServer OPC UA server.

  1. Open the SmartServer Configuration page as described in Accessing the SmartServer IoT Configuration Page.

...

  1.  The Network tab appears as the default SmartServer Configuration page.

...

  1.  Once the network settings are configured for the SmartServer system, then the System tab will appear as the default.

...

  1. image-20250212-194933.pngImage Added

    Image Added


    For SmartConnect, open the SmartServer Configuration page as described in Accessing the

...

  1. SmartConnect Configuration Page.

...

  1. The Configuration view that appears depends on your cache data. As needed, click the SmartServer IoT tab.

...

  1. The System tab (top) will appear as the default as shown below.

...

  1. image-20250212-195033.pngImage Added

  2. Click the OPC UA tab. 

...

  1. Image Added

    image-20250212-195158.pngImage Added

  2. Enable the OPC UA

...

  1. server option

...

  1. .

...

  1. image-20250212-195242.pngImage Added

    image-20250212-195310.pngImage Added

  2. Click Update.

  3. For subscription-based monitoring (event-driven) at the OPC UA client, the Monitored and Polled datapoint setting needs to be enabled on the

...

  1. CMS Datapoint Properties widget. See Defining Datapoint Properties for more information. 

...

  1. image-20250212-195347.pngImage Added


    This setting applies to datapoints on BACnet, LON (using IMM), and Modbus devices. For datapoints on LON devices using DMM, if polling is not enabled for the datapoint, the SmartServer automatically enables event-driver updates from the datapoint.

  2. Launch Cimplicity Workbench and select File → New → Project.

...

  1. Image Added

  2. From the Project Properties window, select the OPC UA Client protocol option. 

...

  1. Image Added

  2. Click OK.

  3. Select Project

...

  1. → Equipment → Ports and set the New Port fields.

...

  1. Image Added

  2. Click OK.

  3. Select Project

...

  1. → Equipment → Devices and set the New Device fields.

...

  1. Image Added

  2. Click OK.

  3. Select the OPC UA DA Configuration tab and update the Endpoint URL field with the SmartServer OPC UA end point. 

    The OPC UA endpoint URL that is used by the OPC UA client to communicate with the OPC UA server is opc.tcp://smartserver-xxxxxxx.echelon.echcorp.com:55000/UA/echopcua-server where xxxxxxx is the SmartServer's install code.

...

  1. image-20250212-195500.pngImage Added

  2. Click Test Connection to test the communication between the GE Cimplicity client and the SmartServer’s OPC UA server.

  3. Select Project

...

  1. → Points → New to add a new point.

...

  1. Image Added

  2. Enter the data for a New Point, including PointID (LuxLevel) and Device (OPC UA device previously added step #11).

...

  1. Image Added

  2. Click OK.

  3. Select the Device tab and click the NodeId button to launch the OPC UA Address Space Browser.

...

  1. Image Added

  2. From the OPC UA Address Space Browser, select the monitored datapoint (nvoLuxLevel in the example below; datatype is an Integer/Uint 16).

...

  1. Image Added

  2. Click OK

  3. Save all the files and click Run to run the project.

...

  1. Image Added

  2. Right-click the LuxLevel point and select Point Control Panel.

...

  1. Image Added


    The Point Control Panel appears.

    The value of the LuxLevel datapoint is 18 in the example below.

...

  1. Image Added