Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  1. Open the SmartServer Configuration page as described in Accessing the SmartServer IoT Configuration PageThe Network tab appears as the default SmartServer Configuration page. Once the network settings are configured for the SmartServer system, then the System tab will appear as the default.


    SmartServer IoT Network tab



    SmartServer IoT System tab

  2. From the Network tab, select the LAN Interface Static IP Address dropdown option and specify the address details. 



  3. Click Update to save your configuration.

  4. Reboot the SmartServer IoT or SmartServer Pi.

  5. For SmartServer IoT, open the SmartServer Configuration page again and click the Firewall tab.



  6. For SmartServer IoT, enable the port 1883 for eth0, which is required for the IzoT Net Export Tool and internal applications.



  7. Click Update to save your configuration.

  8. Click the LON tab.

    SmartServer IoT and SmartServer Pi LON Configuration pages are shown below. The examples that follow are shown using SmartServer IoT.
    Image Removed
    Image Added
    SmartServer IoT LON tab
    Image Removed
    Image Added
    SmartServer Pi LON tab

  9. Enable the SmartServer for IP-852  eth0 interface.

    Image RemovedImage Added
    SmartServer IoT LON tab

  10. Click Update to save your configuration.

  11. Click the CMS tab and log into the CMS.

  12. From the Devices widget, switch the LON management mode to LON Independent Management Mode (IMM).

...

  1. Launch the LonWorks Interfaces (32-bit) control panel applet on your Windows PC.



  2. Using the LonWorks Interfaces applet, add a new IP-852 interface. 

  3. Define an IP-852 VNI interface that will be used by IzoT CT in the LonWorks Interfaces applet.

  4. Launch the EnOcean IP-852 Configuration Server. 

  5. Create or open an existing IzoT CT network and attach to the defined IP-852 interface that is on the same IP-852 channel as the SmartServer.

  6. Set the Management Mode to OnNet.

  7. Verify that the Channel Properties of the opened network is set to IP-852.

  8. Create and add new IP-70 channel that represents the internal IP-70 channel.

  9. Add a new router object to the drawing connecting the IP-852 channel to the newly defined IP-70 channel.

  10. Return to the SmartServer LON Configuration page.

  11. Click IP-852 Router Configuration → Service/Connect button to generate service connect messages for commissioning the router.
    Image Removed
    Image Added
    SmartServer IoT LON tab

  12. Drop a device on the IP-70 channel and commission it using the SmartServer XIF and the LON Configuration page Service/Connect button.

  13. Drop a device on the IP-70 channel and commission it using the SmartServer internal application XIF file to expose the datapoints on the LON network. At this point, the outputs for the LON datapoints on the SmartServer internal application device should be active and populating live datapoints.